Hydro Mining Radiators & Cooling Systems | Lianli Equipment

External heat rejection and coolant management equipment for hydro-cooled ASIC mining operations. This category includes Lianli radiators, CDUs (Coolant Distribution Units), and the Lianli 28-unit cooling cabinet system designed to support up to 28 hydro-cooled miners in a single integrated infrastructure. Hydro miners generate significant heat that must be dissipated through external radiators or dry coolers. The cooling loop circulates a water-glycol mixture through the miner's heat exchangers, absorbs the thermal load, and transfers it to these external units for rejection. Proper radiator sizing depends on the total wattage of your hydro fleet and the ambient temperature at your facility. Lianli (Dongguan Lian Li Electronics Technology) is a specialist manufacturer of liquid cooling solutions for data centers and mining operations. Contact the team for sizing guidance, pricing, and compatibility with your hydro miner fleet.

5.0
estrela estrela estrela estrela estrela
4.97
estrela estrela estrela estrela estrela
4.5
estrela estrela estrela estrela estrela
Hydro Mining Radiators & Cooling Systems | Lianli Equipment
grade de colmeia grade de colmeia
Filtrar & Ordenar

Nenhum produto encontrado

Tente ajustar seus filtros ou termo de pesquisa

Equipamento Verificado

Cada unidade testada antes do envio

Envios Rápidos

Envio em 1–3 dias úteis para unidades em estoque

Cripto Aceito

Pague com BTC, ETH, USDT e mais

Especialistas em Resfriamento

Ajuda na dimensionamento do seu sistema hidropônico

Infraestrutura de Rejeição de Calor

O Radiador: O Componente Mais Crítico em Qualquer Circuito de Refrigeração Hidráulica

Um sistema de mineração ASIC resfriado a líquido é tão eficaz quanto sua capacidade de rejeitar calor para o ambiente. O radiador — também conhecido como cooler seco, troca de calor externa ou radiador CDU — é a última etapa do ciclo de resfriamento: ele absorve o calor dos seus miners ASIC e o transfere para o ar ao redor. Subdimensionar o radiador é o erro mais comum em configurações de hidro DIY, e o mais provável de causar falhas prematuras no hardware ou limitação térmica.

Faixa Disponível

4.5–85 kW

Para corresponder a qualquer tamanho de sistema hidrelétrico

Resfriamento Livre

~0 W

Potência do ventilador em climas frios abaixo de 15°C

Ruído vs Arrefecido a ar

−35 dB

Sistema hidrológico vs rack equivalente a arrefecimento a ar

Implantação

Interno & Externo

Montagem na parede, suporte de chão ou telhado externo


Como Funciona

O papel do radiador em um circuito de resfriamento por mineração hidro

Em um ciclo de resfriamento por hydro, o refrigerante absorve o calor dos chips da placa hash dentro de cada máquina Antminer Hydro. Essa água aquecida — agora 10–20°C mais quente do que quando entrou — sai pelas conexões rápidas posteriores e retorna pelo coletor de retorno até o radiador. Dentro do radiador, o refrigerante quente passa por uma série de aletas e tubos de metal, enquanto ventiladores puxam o ar ambiente através do conjunto de aletas. O calor é transferido do líquido para o ar e é exaurido para longe da unidade.

Em climas frios (ambiente abaixo de aproximadamente 15°C), a diferença de temperatura entre o refrigerante aquecido e o ar externo é grande o suficiente para que os ventiladores possam operar em velocidade mínima — ou, em climas verdadeiramente congelantes, com quase zero de potência — e ainda assim obter uma rejeição de calor adequada. Isso é chamado de "resfriamento gratuito" e representa uma das vantagens econômicas mais significativas da mineração hidroelétrica no norte da Europa: a eficiência energética (PUE) pode se aproximar de 1,0 durante os meses de inverno.

O radiador é dimensionado em kilowatts de capacidade de refrigeração a uma determinada temperatura ambiente. Uma regra comum para dimensionamento excessivo é selecionar um radiador com capacidade de 120% do seu consumo total de energia ASIC — por exemplo, um radiador de 12 kW para uma configuração que consome 10 kW no total. Essa margem de segurança leva em consideração temperaturas ambientes mais altas no verão, quaisquer ineficiências no fluxo e expansão futura de capacidade.

Guia de Dimensionamento de Radiadores

Escolha a Capacidade Adequada para a Sua Configuração

4.5–6 kW

Unidades Antminer Hydro 1–2

Radiador compacto de parede. Ideal para configuração hidráulica residencial pequena ou bancada de testes com uma única máquina. Para uso interno ou ao abrigo ao ar livre.

10–12 kW

3–4 unidades Antminer Hydro

Unidade de piso de gama média ou montagem na parede. Capacidade mais popular para pequenos racks de 3 a 4 máquinas.

20–30 kW

Unidades Antminer Hydro 6–10

Cooler seco de chão maior, adequado para implantação completa de uma única prateleira. Frequentemente utilizado ao ar livre com mistura de glicol.

40–60 kW

Unidades Antminer Hydro 12–20

Radiador CDU integrado no rack ou refrigerador seco de circuito múltiplo. Construção de nível comercial para instalação permanente ao ar livre.

85 kW +

25–30+ unidades Antminer Hydro

Estante industrial CDU. Rejeição de calor na implantação total da estante. Conecta-se a manifolds de distribuição de múltiplos circuitos.


Onde os radiadores são utilizados

Três Contextos de Implantação para Radiadores Hidro

Radiadores hidráulicos cumprem diferentes funções dependendo da configuração do seu sistema — de instalações independentes de uma única máquina até infraestrutura de CDU em rack.

Configurações de ASIC Hydro independentes

Uma única máquina Antminer Hydro consome cerca de 5,5 kW. Operando de forma independente, ela necessita de um radiador externo de 4,5 a 6 kW conectado por mangueira às suas conexões rápidas traseiras. O radiador pode ser fixado na parede na mesma sala, em um corredor ou passar por uma parede para um local externo. Uma pequena bomba (frequentemente a própria bomba interna da máquina mais uma unidade inline adicional) faz circular o refrigerante. Esta é a configuração hydro de nível básico.

Tamanho típico do radiador

4,5–6 kW

Gaiolas Hidráulicas de Estrutura Aberta

Um rack de mineração completo com 8 a 12 máquinas Antminer Hydro consome um total de 44 a 66 kW. Isso requer um radiador externo ou refrigerador a seco na faixa de 50 a 85 kW, normalmente de chão ou montado fora do edifício. Um coletor de fornecimento distribui o líquido de resfriamento do circuito do radiador para a conexão rápida de cada máquina; o coletor de retorno recolhe a água aquecida de volta. Essa é a configuração padrão de hidrojá de escala de rack.

Tamanho típico do radiador

50–85 kW

Armários de Racks Compatíveis com Hidráulica

Alguns armários de rack fechados são projetados para mineradores ASIC hidroscompatíveis e incluem um radiador integrado dentro do gabinete, rejeitando o calor por meio de uma tubulação traseira ou plenum superior. Isso cria uma unidade de mineração hidrostática totalmente fechada e quase silenciosa. Um radiador externo ainda é necessário para configurações de gabinetes maiores, onde o trocador de calor interno não consegue suportar toda a carga térmica — particularmente para gabinetes com mais de 10 máquinas em condições ambientais mais quentes.

Tamanho típico do radiador

10–30 kW (suplementar)


Perguntas Frequentes

Perguntas Comuns sobre Radiadores de Água

A mining radiator (dry cooler) is an outdoor heat exchanger that rejects heat from a hydro cooling loop into the ambient air. It is the final stage of heat rejection in any hydro-cooled ASIC mining setup — essential for keeping coolant temperatures within operating range.

Start with your total ASIC power draw: three Antminer S21 Hydro at 5.5 kW each = 16.5 kW heat load. Select a radiator rated at 120-130% of that figure (20-22 kW). For hot climates (35C+), increase to 140-150%. Contact us with your miner count and site location for exact sizing.

The CDU circulates coolant through your miners, then routes heated coolant to the radiator for heat rejection. The radiator returns cooled fluid to the CDU, completing the loop. CDU and radiator must be matched for flow rate and thermal capacity. Browse our mining equipment for compatible CDU options.

Bitmain radiators are designed specifically for their Hydro miner ecosystem with guaranteed compatibility. Third-party dry coolers often offer higher capacity and better value at larger scales. Both work with standard hydro fittings. Contact us for recommendations based on your fleet size.

Small radiators (4.5-12 kW) can operate indoors with adequate ventilation — the radiator exhausts hot air into the room. Larger units (20 kW+) should be outdoors or in dedicated mechanical spaces. Outdoor installation requires glycol coolant to prevent freezing in cold conditions.

Radiator noise depends on size and fan speed. Small units (4.5-12 kW) produce 45-55 dB. Large industrial dry coolers (50+ kW) can reach 60-70 dB at full speed. Variable-speed fan controllers reduce noise during cooler ambient conditions. For noise-sensitive sites, contact us for low-noise options.

Clean radiator fins seasonally to remove dust and debris that reduce airflow efficiency. Check fan operation quarterly. Inspect hose connections for leaks. Test coolant chemistry every 3-6 months. Well-maintained radiators operate reliably for 10+ years. See our FAQ for detailed schedules.

Radiators are compatible with any hydro mining system that uses standard water/glycol coolant loops — including all Bitmain Antminer Hydro models. The key is matching thermal capacity (kW rating) and coolant flow rate to your setup. Contact us to confirm compatibility with your specific miners.

Radiator fan power is typically 1-5% of the total mining power draw. A 20 kW radiator may use 200-500W for its fans. Variable-speed controllers reduce consumption in cool weather. This is significantly less than air-cooled ASIC fan power, contributing to hydro cooling's superior PUE.

Yes — all radiators and dry coolers ship with free worldwide DDP delivery. No customs duties or import taxes. We handle all logistics, packaging (with protection for fins and fittings), tracking and insurance.

Yes — we offer custom dry cooler configurations for specific capacity requirements, non-standard mounting arrangements and specialised environments. Contact our team with your thermal load, space constraints and site conditions for a tailored solution.

Yes — volume B2B pricing is available for multi-unit radiator and cooling equipment orders. Contact our B2B team with quantities and specifications. We offer combined radiator + CDU + miner + hosting packages for complete hydro deployments.

For indoor setups where ambient temperature stays above 5C, use deionised water with corrosion inhibitor. For outdoor radiators or cold climates, use water-propylene glycol mix — 30% glycol for protection to -15C, 40% for -25C. We stock both corrosion inhibitor and premixed glycol coolant.

Radiator capacity depends on the temperature differential between coolant and ambient air. In hot weather (35C+), effective capacity drops 20-30%. In cold weather, radiators achieve "free cooling" with minimal fan power. Size your radiator for worst-case summer conditions to ensure year-round performance.

For mission-critical operations with 10+ hydro miners, redundant radiators are recommended. If a single radiator fails, your miners will overheat within minutes. Dual radiators with automatic failover protect your fleet. Contact us for redundant cooling system design.

Mount radiators with unrestricted intake and exhaust clearance — typically 1-2 metres minimum on all sides. Avoid recirculation where hot exhaust air feeds back into the intake. Wall-mounted units should exhaust away from the building. Multiple radiators should be spaced to prevent thermal interference.

Quality dry coolers use copper or aluminium fin-and-tube construction with corrosion-resistant coatings. Stainless steel fittings prevent galvanic corrosion. For coastal or high-humidity environments, specify marine-grade coatings. Proper coolant chemistry (corrosion inhibitor) protects internal loop surfaces.

Well-maintained radiators last 10-15+ years. Fan motors are typically the first component to need replacement (5-8 years). Fins and tubing are durable if coolant chemistry is maintained. Regular cleaning and corrosion inhibitor replenishment extend operational life significantly.

Many modern CDUs include temperature and flow monitoring with remote access. Adding inline temperature sensors and flow meters to your radiator loop provides real-time performance data. For hosted setups, our monitoring dashboard tracks cooling system health continuously.

Our team provides free hydro system design consultations including radiator sizing. Contact us via WhatsApp, email or phone with your miner count, site location and climate. Visit our FAQ for instant answers to cooling questions.

Precisa de ajuda para dimensionar seu radiador?

Navegue pela nossa linha de radiadores acima e filtre pela capacidade de resfriamento. Se você estiver montando um sistema hidro completo e quiser uma lista de componentes confirmada — radiador, bomba, coletores, mangueiras, fluido de arrefecimento — entre em contato com nossa equipe. Fornecemos tudo o que é necessário para um ciclo hidro completo e oferecemos especificações gratuitas do sistema para clientes que adquirirem equipamentos conosco.